View Categories

Types of pressurisation and EPL

2 min read

Type pxb is a type of pressurised enclosure that provides an equipment protection level Gb (or Mb or Db).

This means that when a pxb enclosure is located in an area requiring Gb (e.g zone 1), it establishes non-hazardous conditions within the enclosure.

Type pyb pressurised enclosure provides equipment protection level EPL Gb (or Db) with EPL Gc (or Db) internal to the enclosure.

This means that normally, when a pyb enclosure is located in an area requiring Gb, it establishes conditions requiring Gc within the enclosure. The equipment inside must be suitably protected, but restricted breathing Ex nR is not allowed!

A type pzc pressurised enclosure provides equipment protection level Gc (or Dc)
This permits unprotected equipment within the enclosure.

The type of pressurisation to be used depends on

  1.  The required EPL for equipment in the location concerned – Gb for Zone 1 or Gc for    
     Zone 2 (unless  a risk assessment has determined otherwise),
  2. The likelihood of an internal release of gas, and
  3. Whether the equipment within the pressurised enclosure is ignition capable.

From IEC60079-2: 2014, Table 1, the required pressurisation type for the enclosure in a gas atmosphere is as shown below. The shaded portion applies when there is no internal source of release.

Flammable substance in containment system (C.S)External Area EPL/CAT.Equiv. ZoneEnclosure contains ignition-capable equipmentEnclosure does not contain ignition-capable equipment
No C.S.Gb / 21Type pxbType pyb*
No C.S.Gb / 32Type pzcType pzc
Gas or VapourGb / 21Type pxbType pyb*
Gas or VapourGc / 32Type pxbType pyb*
LiquidGb / 21Type pxb (inert gas)**Type pxb (inert gas)**
LiquidGb / 32Type pzc (inert gas)**Type pzc (inert gas)**

For enclosures with no internal flammable release, the required type of protection can be summarised as shown below, from Iec60079-14: 2013, Table 16

External EPLEnclosure contains equipment not meeting EPL “Gc” requirementsEnclosure contains equipment that meets EPL “Gc” requirements
GbType pxbType pyb
GcType pxb or pzcNo pressurisation required