Obstruction to Flamepaths

IEC / BS EN60079-14 states that the obstruction of flanged joints must be avoided, unless the equipment has been tested at smaller distances than those shown in the table below.

A solid object such as a wall, steelwork, conduit, bracket, or other equipment etc., in close proximity to the opening at the joint can, in the event of an internal explosion, reduce the efficiency of the flamepath to the extent that ignition of the external gas could occur.

the minimum distance between a flamepath and a obstruction
‘d’, the minimum separation between a flamepath opening and an obstruction.

The minimum separation distances between the flamepath opening and an obstruction, as specified in 60079-14 are:

Gas SubdivisionDistance
IIA10mm
IIB30mm
IIC40mm